一、Application
GLC79-400/3.6,GLC79-400/3.6(S),GLC79-400/3.6(D),GLC79-800/3.6,
GLC79-800/3.6(S),GLC79-800/3.6(D) isolating phase change switch (hereinafter referred to as isolator), which are used in the
large volume explosion-proof electromagnetic starter of AC 50Hz, voltage to
3.6kV, current to 400A (800A) for mining, as the isolation of main circuit and
changing the phase sequence of the current at the condition of load. This switch
can replace imported products. There is a reliable auxiliary contact installed
in the isolator. Isolating phase change switch can be with
test location or ground position and meet a variety of
application requirements of the customers.
二、P/N meaning

三、Type
Type: manual air
three-phase isolating phase-change type
四、Normal working conditions
1. Altitude: no more
than 2000m
2. Ambient
temperature: -25℃-+45℃
3. Relative Humidity
is not exceed 90%, and the average lowest temperature of the ground is 25℃.
4. In the environment of no
gas or steam which will not break the metal and insulating material.
5. The location of no severe
vibration and shock
6. The location of
prevent dripping
五、Structure
The outline of the isolator is shown as picture 1-6.
The structure of the isolator is rotary style,
±45°.
The contact of the isolator is dual fracture rotary style, divided into moving
contact and static contact. There are pressure spring in the static contact to
ensure the pressure of the contact. Contact has the characteristics of high
level isolating withstand voltage, bear big current, strong capability of
self-cleaning, etc. The rotation of the contact is located by the mechanism to
ensure the reliable operation of the isolating switch. The insulating parts of
the isolating switch are composed of insulated panel, insulation baffle, static contact insulation base, insulation
sleeve and so on, which can ensure the insulation performance of the ground,
phase-phase and fracture of the isolating switch. The insulation parts adopt DMC
repression, have good mechanical performance and electrical insulation
performance.
The operation of the insulator. The main axis drives the
contact to rotate( of which the test and ground circuit rotate forward 90 °), at
the same time, drive the location cam rotate, make the location spring storage
energy. When the main axis is rotating, the location spring release energy and
help the contact to reach the purpose of opening and closing, the auxiliary
contact also converts.
六、Installation, using and maintenance
1.
The mounting size of the insulator shown as
picture 1-6.
2. When the main circuit is connected at output end, a & c
phases at one end(up), b phase at another end(below). When the operating axis in
the zero position, the main circuit is at isolated condition; Operating axis
rotates clockwise to connection condition, input and output phase sequence is
the same, positive connection; Operating axis rotates counter-clockwise to
connection condition, the input and output phase sequence A & B conversion,
backward connection. Circuit schematic shown in picture 7, A, B, C are input
end, a, b, c are output end.
3. During operation the moving parts should keep flexible,
and the moving parts can be put on a small amount of lubricating oil. Regularly
check the working status of the contacts, the contact should be inspected in
time to see if there is any over travel if the contact has something unusual,
and make the necessary adjustments.
|