Vacuum circuit breaker is suitable for the circuit of AC 50Hz, rated voltage 1140V and below this level, rated current 630A and below this current level, as the total switch, branch switch of the power supply system, and also can be used as the starting for large volume motor. It is also suitable for a variety of distribution switches made up by various kinds of protection devices, especially for the coal mine explosion-proof vacuum feed switch.

 

一、Ambient condition

Altitude: no more than 2000m

           Ambient tenperature:-25℃-+40

           Relative Humidity: not exceed 95 at +25

           The inclination of the mounting position and vertical is no more than 15°.

           No gas and conductive dust damage the insulation in the surrounding environment.

             

二、Basic model 

           Main circuit poles: three poles (NO)

           Auxiliary contact: two NO, two NC

           The circuit breaker is electromagnetic           

           closing, mechanical latching (when the under voltage coil is energized).

           Circuit breaker is with shunt tripper, under voltage tripper and manual opening.

             

三、 Structure and working principle

The circuit breaker is composed of three vacuum tubes, installed in insulated bracket. There is over-travel spring at the moving conductive rod end, which can increase the contact pressure and reduce the contact bounce. The moving conductive rod is connected through the connector screws, the arm and the closing electromagnetic system. There are the opening spring and the maintaining hook installed on the armature plate, which can make the circuit breaker mechanically latching in the closing condition. The other end of the maintaining hook is fasten by the opening rotation axis, which is mechanically controlled by the shunt coil,  under voltage coil and manual tripper, make the opening rotation axis rotate and trip to achieve the purpose of opening.

 

The circuit breaker adopts two level tripping mechanism, which can make the circuit breaker keep the closing condition at a minimum power (under voltage coil energized), and it can also compose of various distribution switch with various protection devices. Two level tripping make the control power of the breaker power small, and the opening time short.

 

四、Acting procedure of the circuit breaker

1.Closing: receiving the closing instruction, the closing coil is energized, electromagnet is excited and absorpt the armature. On the one hand, compress the opening spring to storage energy; on the other hand,  drive the arm action to make the vacuum interrupter closing, at the same time the maintaining hook turns, fasten by the opening rotation axis(at the condition of the under voltage got electric pick-up) to achieve the mechanical latching, converse with the external auxiliary contacts, after a group of contacts delayed (delay 50ms to 100ms through the external circuit ), cut off the closing coil power. The whole closing action is completed.

 

2.Opening: receiving the opening instruction, the shunt coil are imposed rated control supply voltage, under voltage coil de-energizing (the voltage drop to 35% and below of the rated control supply voltage) or by the manual opening (these three can be activate simultaneously), at this time, the opening rotation axis rotate to trip, the armature and the maintaining hook rotate under the action of the opening spring, through the arm to make the vacuum interrupter cut off the circuit, and at the same time, the auxiliary switching conversion, the closing is completed.

 

六、Additional instruction

  1.When the circuit breaker is breaking the inductive load, it must be added RC protection or varistor protection to prevent over-voltage operation.

   2.When the circuit breaker is closing the circuit that has Yufu short-circuit fault, it must be taken the  measures of "jump" preventing by the method of electric.( after close the short circuit and automatic closing, even if the closing instruction has not been relieve, it will not be re-closing), such as installing the "jump" preventing relay.

   3.The electric schematic of the control circuit: see picture 1.

 

 

Picture 1

 

 

七、Preparation before operation

1.For the outline and mounting dimension of the circuit breaker, see picture 2. Pls read the instruction carefully before installation.

2. The circuit breaker must be checked and tested before put into operation.

2.1 Checking if the connection part is loose, and make the appropriate treatment.

2.2 Checking if the operating characteristics is reliable, it must be operate and can not be mis-operate, the auxiliary switch converts reliably, which can be checked according to the third requirement.

2.3 If allowed the circuit breaker should do the following required voltage test for 1 minute, no arcing or flashover phenomenon.

a. The voltage between the moving and static contact of the vacuum interrupter is 10KV.

b. The voltage between phase and phase, phase and ground is 4.2KV.

 

3.When installing the circuit breakers, the main conduction circuit should be connected to the load of the power by a suitable conductor, the size of the conductor must meet relative requirements.

After connection, it should ensure the vacuum interrupter does not produce stress to avoid damaging the vacuum interrupter or changing the distance between the moving and static contact, affecting the contact resistance of the contact.  

 

八、Maintenance and repair

  

The maintenance purpose is to keep the performance of switching device, find the problem earlier to take preventive measures. Generally the maintenance is divided into regular maintenance and trouble hunting.

1. Regular maintenance (see table 1)

2. Trouble hunting (see table 2)

3. The circuit breaker will be out of operation when one of the following status occurs during operation:

  a. operation times reach to the technical condition specified life.

  b. after opening and closing the short circuit current.

 

Table 1

No.

Inspection items

The main inspection items

cycle

Note

1

opening and closing action

opening and closing the circuit breaker for many times, check if the stroke overtravel is normal

one time/3 months

 

2

 

the general check of the outside conduction circuit

checking the fastener of the main conduction circuit  

 

 

one time/3 months

 

3

Operating mechanism

checking the fastener of the control circuit, rotate the friction part and add lubricant.

 

one time/3 months

 

4

cleaning of each part

each insulating parts, auxiliary switch and contact, etc. on the surface of the vacuum interrupter

 

one time/3 months

 

5

test items

 

test the insulating resistance between the main circuit contacts, main circuit and the control circuit to ground.

 

withstand voltage test between the contacts of the main circuit.

one time/year

the insulating resistance of the main circuit is 100MΩ, the control circuit to ground is above 2MΩ, the withstand voltage between the main circuit contacts is 10KV/1min, no arcing or flashover phenomenon.

 

 Table 2

fault

status

fault reason

judging method

disposition

Closing and no operation.

Control circuit has no voltage, incorrect wiring and plug

Test the power supply voltage by universal meter, which should be consistent with the relevant specification of the instruction.

According to the specification of the instructions,  wiring correctly so that each coil imposed the required rated control supply voltage

the coil burned or broken

Checking by universal meter

Change the coil or repair the broken wire

diode arcing

Replace the diode

The terminals of the two coils connected reverse. 

Reverse connection

Change to correct connection.

Closing, and mechanical hook can not work

 Control power supply voltage is too low.

Test the power supply voltage by the universal meter to see if it is up than 70% of the rated control power supply voltage.

Reduce the voltage drop and increase the control power supply voltage.

Energized time of the closing coil is short.

Increase the delay time according to the electric schematic

Increase the capacitance

The mechanism of the closing part is stuck.

 

Checking if the closing  electromagnet and armature are in the place

 

Adjustment

The vacuum interrupter is broken

Checking if the interrupter has crack and breakage, if there is no negative pressure, if the withstand voltage between the contacts has arcing.

replace interrupter

the maintaining hook is not in place

 

The reason that the maintaining hook can not pass opening rotation axis: tension spring force of the maintaining hook is small; the rotation angle of the opening rotation axis is excessive; the re bounce of the tension spring force on the rotation axis is excessive.

Readjust

the maintaining hook can not fasten.

The maintaining hook passed the opening rotation axis, but after the closing coil is cut off the electricity, the maintaining hook can not fasten, the reason; the rotation angle of the opening  rotation axis is too small, the re bounce of the tension spring force on the rotation axis is small.

Readjust

 

The reason of the under voltage tripper unfasten: under voltage coil burned, the applied voltage to the under voltage coil is not correct, the travel of the  plate is too small, making the pick up voltage of the under voltage coil is too high.

Change the under voltage coil or increase the voltage, adjust the plate to make the pick up voltage of the under voltage coil below 75% of the rated control power supply voltage.

not opening

Under voltage tripper can not trip.

The spring force of the under voltage tripper is small, the travel of the plate is too big.

 

The tension spring force of the maintaining hook is too big, which makes the force of the maintaining hook is big.

readjust

Shunt tripper can not trip.

Rotation angle of the opening rotation axis is too big, which makes the stroke of the shunt electromagnet increased, and the pick up voltage is too high, the coil burned.

replace the coil

Manual open it and  can not trip.

the screw loosed or the manual operation is not in place.

Readjust

The closing coil is not cut off the electricity.

 

The contacts of the middle relay and auxiliary switch are not breaking.

Change the relay or auxiliary switch, readjust and clean the contact.

mechanism stuck

Manually making and breaking for several times.

readjust

 

the contact of the vacuum interrupter fusion welding

checking by universal meter

replace the vacuum

coil burned

closing coil or shunt coil burned

the rated control power supply voltage is inconsistent, auxiliary switch can not be breaking, make the coil energized for a long time.

Change to the correct rated control power supply voltage, adjust or replace the auxiliary switch and coil.

under voltage coil burned

short circuit due to bad insulation

replace the coil

arcing

The vacuum interrupter lost vacuum

test the withstand voltage of between the contacts is 10KV/1min, arcing,  even if applied voltage repeatedly, the pressure can not be increased.

replace the vacuum  interrupter

temperature of the main circuit is too high

 

fastening screw loosed

checking each fastening screw of the main circuit

tighten the screw

no overtravel

Checking if there is overtravel after several times making and breaking.

readjust

the contact wears excessively

conductive rod short (compared checking)

 

replace the  interrupter